Plenty of tankless jobs in Ontario and BC start with an old gas water heater vented through plastic pipe, and whether that vent can stay changes the quote. Both provincial regulators have published guidance on it, and the short version is consistent: plastic gas vent must be certified to ULC S636, and an appliance replacement is the point at which an older, uncertified vent is expected to go. This is an explainer drawn from those documents, not a news story; the guidance itself is years old.
The rule both regulators start from
The short answer: plastic vent must be ULC S636 certified, and the requirement bites at replacement.
TSSA's Fuels Safety advisory FS-101-07, first issued April 16, 2007 and revised April 7, 2014, says clause 8.9.6 of CSA B149.1 requires plastic vents to be certified to ULC S636, the standard for Type BH gas venting systems. It explains that the requirement followed investigated failures in existing plastic vents, mostly ABS pipe and fittings, including stress cracking and melting, which could create a carbon monoxide hazard.
The advisory gives a water heater example directly: when an existing water heater is replaced, the existing plastic venting must be completely replaced with a certified ULC S636 system. It is not retroactive; existing appliances and vents need no action until the appliance is replaced.
Technical Safety BC's plastic venting directive, issued May 20, 2011, takes the same approach for BC: new and replacement installations need ULC S636 certified vent installed to the manufacturer's certified instructions, and existing systems are left alone until the appliance is replaced.
The narrow exception
The short answer: inspect, replace the first five feet, and pass a pressure test.
Both documents allow the existing vent to stay only where full replacement is impossible or impractical, and only if:
- the first 5 feet of vent downstream of the appliance is replaced with suitable ULC S636 certified vent;
- a visual inspection finds the remaining vent in good working order (cracked or damaged vent can't be repaired);
- a pressure test with air or inert gas at a minimum of 7 inches water column, positive or negative, not exceeding 2 psig, holds at least 75% of the test pressure for at least 5 minutes.
If the vent fails the test, the whole system must be replaced. In Ontario, TSSA treats this as a variance application with fees, a test report and a five-yearly re-inspection condition; its 2014 revision lists the fees, which may have changed since. In BC, the directive also says cellular core vent material is not accepted and must be replaced whenever the appliance is.
What has changed since
The short answer: newer code and standard editions, but no replacement guidance that we found.
Both documents cite older editions of CSA B149.1. Codes have moved on: Manitoba's January 2026 bulletin on the 2025 B149 series notes revised vent clearance tables, for example. The Standards Council of Canada listing shows ULC 636:2026 as the edition that supersedes ULC-S636-08. We found no revised TSSA advisory or BC directive replacing the documents above, so confirm with the regulator before relying on them.
Analysis: how venting should show up in your marketing
This section is TanklessNews.ca analysis, not regulatory advice.
- Quote venting as its own line. Homeowners compare tankless quotes on the headline price. A separate venting line, with a sentence explaining why old plastic vent is usually replaced, protects you from being undercut by a quote that quietly reuses it.
- Explain it on your website once, well. A short page on why vent replacement is part of a tankless conversion, linking the regulator's guidance, answers the question before the estimate visit.
- Use photos you own. If you show vent work, show your own jobs with dates. Never use photos that suggest a cracked ABS vent is acceptable.
- Don't promise a reuse. Whether a vent can stay depends on inspection and testing on the day. Ads that say "no vent replacement needed" set up a dispute.
Our rebate, code and recall content service writes and maintains this kind of page, and our local SEO service makes sure it is found. We are a marketing service, not a gas contractor or inspector. See the full newsroom, or call, text or email.
Frequently asked questions
Does a new tankless heater need a new plastic vent?
Under both the TSSA advisory and the Technical Safety BC directive, replacing an appliance generally means replacing an existing plastic vent with a ULC S636 certified system. Each describes a limited exception that depends on inspection and a pressure test.
Can old ABS vent be reused?
Both documents trace the rule to failures in plastic vents, mainly ABS, including stress cracking and melting. Cracked or damaged vent can't be repaired and must be replaced. Technical Safety BC also says cellular core vent is not accepted and must be replaced when the appliance is.
Are these documents current?
They are the versions we found published in October 2026, but they are old: the TSSA revision is dated April 7, 2014 and the BC directive May 20, 2011, and both reference earlier editions of CSA B149.1. Confirm the current position with your regulator.
What is ULC S636?
The Canadian standard for Type BH gas venting systems, the plastic vent used with many condensing appliances. The Standards Council of Canada database lists ULC 636:2026 as the edition that supersedes ULC-S636-08.
Is this compliance advice?
No. It is a summary of published regulator guidance for marketing and quoting purposes. The installing gas contractor and the regulator decide what a specific job needs.
Sources
- TSSA Fuels Safety Program: Advisory FS-101-07, Plastic Vents (B149.1-10, 8.9.6), revision R1 (2014-04-07)
- Technical Safety BC: Directive, Plastic venting (D-G5 070628 5, revision 5) (2011-05-20)
- Standards Council of Canada: ULC 636:2026, Standard for Type BH Gas Venting Systems (2026-10-23)
- Manitoba Inspection and Technical Services: Gas Bulletin ITS 26-001 (January 2026) (2026-01-12)